MASTERYS GP4

4th generation digital native high performance UPS
Three/three phase from 60 to 160 kVA

Masterys GP4

 System features

• Dual input mains.
• Internal maintenance bypass switch.
• Input mains switch breaker.
• Output switch breaker.
• Auxiliary mains switch breaker.
• Backfeed protection: detection circuit.
• Power walk-in ramp for excellent compliance with generators.
• Common or shared battery for N+1 configuration.

Standard communication features

• 7" touch screen multilingual colour graphic display.
• 2 slots for communication options.
• USB port to download log file.
• Ethernet port for service purposes.

 

 

System options

• External battery cabinet with normal or long-life VRLA batteries.
• High capacity battery charger.
• Alternative backup power technologies:
- NiCd batteries
- Li-Ion batteries
- Li-Ion capacitors
• 3-phase input without neutral.
• Internal backfeed isolation device.
• Common mains coupling bars.
• TN-C grounding system.
• ACS synchronisation system.
• IP21 degree of protection.
• Top cabling kit.
• Top ventilation kit.
• Bypass redundant cooling.
• Seismic fixing kit.

Communication options

• Dry-contact, RS232/485 interfaces.
• MODBUS RTU.
• MODBUS TCP.
• BACnet/IP interface.
• NET VISION: professional WEB/SNMP, ethernet interface for UPS monitoring and remote automatic shutdown.
• Ethernet gateway for cloud sevices.
 

Tehniline info

Sn [kVA] 60 80 100 120 160
Pn [kW] 60 80 100 120 160
Input / output 3/3
Parallel configuration up to 6 units
Input
Rated voltage

400 V 3ph+N (3 wire input also available on demand)

Voltage tolerance

240 V to 480 V

Rated frequency 50/60 Hz ± 10%
Output
Power factor 1 (according to IEC/EN 62040-3)
Rated voltage 3ph + N: 400 V (can be configured 380/415 V)
Rated frequency 50/60 Hz
Frequency tolerance ± 2% (configurable for GenSet compatibility)
Total output voltage distortion - linear load < 1%
Overload 125% for 10 minutes, 150% for 1 minute
Crest factor  3:1
Bypass
Rated voltage rated output voltage
Voltage tolerance ± 15% (configurable from 10% to 20%)
Rated frequency 50/60 Hz
Frequency tolerance ± 2%
Efficiency (TÜV SÜD verified)
Double conversion mode up to 96.5%
Always on mode up to 99%
Environment
Operating ambient temperature from 0 °C up to +40 °C (from 15 °C to 25 °C for maximum battery life)
Relative humidity 0% - 95% without condensation
Maximum altitude 1000 m without derating (max. 3000 m)
Acoustic level at 1 m
(ISO 3746)
< 55 dBA < 60 dBA < 65 dBA
UPS cabinet 
Dimensions W x D x H 600 x 855 x 1400 mm 600 x 855 x 1930 mm
Weight 174 kg 186 kg 228 kg 240 kg 350 kg
Degree of protection IP20
Colours RAL 7016
Standards
Safety EMC IEC/EN 62040-1, AS 62040.1.1, AS 62040.1.2
Performance IEC/EN 62040-3, AS 62040.3
Environmental full compliance with the RoHS EU directive
Seismic compliance on demand, in accordance with the Uniform Building Code UBC-1997 Zone 4
Product declaration CE, RCM (E2376)

Kuidas osta?

Äri- ja erakliendid:
Enamik meie toodetest on saadaval elektrimaterjalide hulgimüügifirmades. Siit leiad meie koostööpartnerid – elektrimaterjalide hulgimüüjad.

Projektimüük, jõuelektroonika tooted, varustus ja erilahendused:
Palun võtke meiega ühendust.

Rohkem infot toodete kohta:

Margus Tiirusson

Mobiil: (+372) 51 39 138